top of page

Case Study: Hydroponic Grow House Fire. But Not the Cause You’d Expect

A residential property in Western Sydney suffered a significant fire that partially collapsed its roof. The home had been illegally converted into a large-scale hydroponic marijuana cultivation operation. The setup included plants in nearly every room and an extensive, unapproved electrical installation to power grow lights and associated equipment.


The tenants, who had used false identification to secure the lease, paid rent exclusively in cash and vacated the property immediately after the fire. We would be lying if we said this was the first time we had heard this story; all they wanted was to reduce the expense of a real estate agent.


There was smoke damage across most of the rooms, but there was severe fire damage to the bathroom and adjacent hallway, with charred framing and a collapsed ceiling. This bathroom had electrical transformers piled along the walls, many showing evidence of heat damage, particularly those lower in the stack.


An inspection of the mains supply revealed two separate single-phase lead-in cables, one legally metered and one illegally bypassing the meter to feed the grow operation directly. Wiring from multiple rooms converged in the bathroom, creating a dense network of cords, adaptors, and transformers.


A charred stack of transformers amidst the aftermath of a bathroom fire, revealing extensive damage and debris.
A charred stack of transformers amidst the aftermath of a bathroom fire, revealing extensive damage and debris.
Key Findings
  • Area of Origin: Bathroom

  • Primary Contributing Factors:

    • Illegal, unmetered electrical feed installed to bypass the meter.

    • A large number of transformers and growth equipment in a confined space with inadequate ventilation.

    • Potential electrical overloading or heat build-up from tightly packed transformers.

  • Cause Classification: Undetermined, minimal excavation was completed due to safety concerns over asbestos exposure.

  • Potential Scenarios:

    1. Electrical overload/fault in wiring or transformers.

    2. Heat accumulation from clustered transformers leading to insulation failure and ignition.


Lessons Learned
  1. Illicit electrical modifications create extreme fire hazards. Bypassing meters removes safety mechanisms and often results in dangerous overloading.

  2. Overcrowded electrical devices in confined spaces are a recipe for overheating. Without adequate heat dissipation, transformers and ballasts can fail catastrophically.

  3. Clandestine drug operations often have hidden fire risks. Investigators and property managers should be alert for tell-tale signs before incidents occur.

  4. Following the scientific method ensures objectivity. Even when the precise ignition point can’t be proven, a structured investigation supports credible findings.


This case highlights how illegal modifications and poor electrical practices can create an environment primed for fire. While the exact ignition mechanism could not be conclusively identified, the conditions in the bathroom, high electrical load, poor ventilation, and unsafe wiring - made a fire almost inevitable.

 
 
 

Comments


  • Instagram
  • LinkedIn
  • Facebook

Tel: + 61 499 522 266
Email: office@originandcause.com.au

IAAI Central Europe
international association of arson investigators
NSW association of fire invesitgators
engineers australia
chartered society of forensic sciences
NZAFI
ANZFSS

Forensic Origin & Cause Investigations acknowledges the Traditional Owners of Country throughout Australia and recognises the continuing connection to lands, waters and communities. We pay our respect to Aboriginal and Torres Strait Islander cultures; and to Elders past and present.

 

© 2025 by Forensic Origin and Cause Investigations. All rights reserved.