As lithium-ion battery-related fire claims increase, insurers need more than an identified ignition source. They need reliable evidence about how a battery was sourced, used, charged, stored and maintained.

Lithium-ion batteries are now commonplace in Australian homes and businesses, powering everything from mobile phones and power tools to e-bikes, commercial equipment and energy storage systems.

In November 2026, Australian insurer Suncorp was reported as stating that home insurance claims linked to lithium-ion battery fires had almost doubled between 2023 and 2026. Importantly, this is an insurer-reported trend, not an independently verified national statistic. The underlying claims dataset has not been publicly released.

For brokers, underwriters and claims professionals, this growing exposure raises an important question:


What information should be collected during a fire investigation to support informed risk and claims decisions?

Five Areas Every Battery Fire Investigation Should Document

1. Battery provenance: where did it come from?

Establish the battery's manufacturer, model, chemistry, capacity, serial number and supplier. Obtain purchase records, product specifications, safety certifications and recall information where available. Determine whether the battery was supplied with the original equipment or purchased separately.

2. Charging practices: how was it being charged?

Record whether the battery was charging at the time of the incident, the charger and power supply used, and their compatibility with the battery. Document charging duration, electrical connections, adaptors, extension leads and any available battery management system (BMS) data. Examine the condition of the charger, connectors and associated wiring.

3. Storage conditions: where was it kept?

Document the battery's location, proximity to combustible materials, surrounding temperatures and potential exposure to moisture or physical damage. For commercial premises, record battery quantities, charging arrangements, storage procedures, fire protection measures and how damaged or defective batteries were managed.

4. Modifications and maintenance: had anything changed?

Identify replacement cells, aftermarket chargers, altered wiring, modified control systems and repairs. Obtain service records and establish whether the battery had previously experienced impacts, overheating, swelling or operational faults. A modification may be relevant to the investigation, but its presence does not automatically establish causation.

5. Product failure: what does the physical evidence establish?

Examine the battery cells, pack construction, protective circuitry, connections and surrounding electrical components. Consider internal cell failure, external short circuits, charging-system faults and exposure to an unrelated fire. Specialist examination or laboratory testing may be necessary.

Crucially, a battery involved in a fire is not necessarily the battery that caused it. Thermal runaway may occur following an internal failure or when a battery is exposed to heat from another fire source. It could even be due to the battery charger itself.

Evidence First. Coverage Decisions Separately.

A scientifically supported fire investigation should establish the origin and cause of the fire, assess competing hypotheses and clearly identify any limitations.

Contemporaneous photographs, witness accounts, CCTV, charging records, product documentation and properly preserved physical evidence can be critical.

The investigation may establish whether a battery initiated the fire, contributed to its development or was simply damaged by an external fire.

However, technical causation is not the same as policy coverage, non-disclosure or liability. Those questions require separate consideration of the policy wording, information provided during underwriting, applicable legal obligations and the circumstances of the loss.

The Takeaway for Insurance Professionals

Battery fire investigations should not stop at identifying a damaged battery. Understanding its history, operation and environment provides a stronger foundation for underwriting, risk engineering, claims assessment and potential recovery opportunities.

For brokers and underwriters, these same evidence categories offer a practical framework for asking better questions before a loss occurs.

Better documentation leads to better-informed decisions, without allowing assumptions about coverage or responsibility to influence the scientific investigation.

Forensic Origin & Cause Investigations (FOCI) provides independent, evidence-based fire investigation services to insurers, loss adjusters, legal professionals and commercial clients across Australia.


Comments


Forensic Origin & Cause Investigations Pty Ltd acknowledges the Traditional Owners of Country throughout Australia and recognises the continuing connection to lands, waters and communities. We pay our respect to Aboriginal and Torres Strait Islander cultures, and to Elders past and present.

 

© 2026 by Forensic Origin and Cause Investigations. All rights reserved.

AU Awards 2026 Digital Badge_Finalist.png
b6d86c88-f0b0-c787-4b57-6dddba6710fd.jpg
bottom of page